A general-purpose PowerLoop interface designed for third party detectors connected to the AutroSafe integrated fire and gas system and AutroSafe maritime gas detection system.
PowerLoop 4-20 mA input unit is a general-purpose PowerLoop interface designed for third party detectors connected to the AutroSafe integrated fire and gas detection system.
The unit has a 24 VDC/400 mA supply output providing power to the connected detectors, plus a 4-20 mA input galvanically isolated from the PowerLoop, and is an EEX me version including 9,5 W 24 V DC/DC for external detector power supply.
The unit comprises the SelfVerify® function. This function ensures the highest grade of reliability and reduces the need for manual testing, because all units comprising this function are automatically checked once every 24 hours.